HV Switchgear

KYN61-40.5 Metal-Clad Withdrawable Switchgear

Indoor 40.5 kV armoured withdrawable switchgear up to 3150 A / 31.5 kA — floor-rolling breaker truck, composite-insulated vacuum breakers with 10,000-operation life, forced mechanical five-prevention interlocks.

Factory-direct supply Worldwide delivery & export documentation 12-month warranty · extended options
  • Assembled cabinet structure; breaker truck of floor-rolling type
  • New composite-insulated vacuum breakers — fully interchangeable and easy to replace
  • Lead-screw propulsion in the truck frame moves the breaker effortlessly and prevents damage from mal-operation
  • All operations performed with the door closed
  • Forced mechanical interlocking between main switch, truck and door fulfils the complete five-prevention功能
  • Spacious cable compartment connects multiple cables; fast earthing switch for earthing and short-circuit makin
At a glance

Built to perform, year after year

40.5 kV / 50 Hz
Rated voltage / frequency
1250 / 1600 / 2000 / 3150 A
Rated current
20 / 25 / 31.5kA
Short-time withstand current (4 s)
50 / 63 / 80kA
Peak withstand current
A closer look

Engineered around safety, efficiency and uptime

Overview

The KYN61-40.5 armoured withdrawable AC metal-enclosed switchgear is an indoor complete distribution assembly for three-phase 50 Hz, 40.5 kV systems. Serving power plants, substations and industrial enterprises for receiving and distributing power, it provides circuit control, protection and monitoring, and also suits frequently operated installations.

Executive standards

GB/T 3906-2020 — 3.6–40.5 kV AC metal-enclosed switchgear and controlgear
IEC 60298-1990 — AC metal-enclosed switchgear and controlgear above 1 kV up to 52 kV
GB/T 11022-2020 — Common technical requirements for HV switchgear and controlgear

Structural characteristics

Assembled cabinet structure; breaker truck of floor-rolling type
New composite-insulated vacuum breakers — fully interchangeable and easy to replace
Lead-screw propulsion in the truck frame moves the breaker effortlessly and prevents damage from mal-operation
All operations performed with the door closed
Forced mechanical interlocking between main switch, truck and door fulfils the complete five-prevention功能
Spacious cable compartment connects multiple cables; fast earthing switch for earthing and short-circuit making
Enclosure IP4X; IP2X with the truck-compartment door open

Service conditions

Ambient −10 °C … +40 °C, 24 h average ≤ 35 °C; altitude ≤ 2000 m
Daily RH ≤ 95 %, monthly ≤ 90 %; vapour pressure ≤ 2.2 kPa daily / 1.8 kPa monthly
Seismic intensity ≤ 8; site free of fire/explosion hazard, heavy pollution, chemical corrosion and severe vibration

Installation

Electrical-room height ≥ 4500 mm; rear clearance to wall ≥ 1500 mm
Foundation flatness ≤ 1 mm/m²; embedded channel ≤ 3 mm above floor; fix by bolts or welding
Cabinet weight ≈ 1800 kg; operating corridor ≥ 3000 mm (single row) / ≥ 4000 mm (double row face-to-face)

Technical specifications

Full specifications

Switchgear parameters
Rated voltage / frequency
40.5 kV / 50 Hz
Rated current
1250 / 1600 / 2000 / 3150 A
Short-time withstand current (4 s)
20 / 25 / 31.5 kA
Peak withstand current
50 / 63 / 80 kA
PF withstand / lightning impulse
95 kV·1min / 185 kV
Protection degree
IP3X
Vacuum circuit breaker
Rated voltage / current
40.5 kV · 1250–3150 A
Short-circuit breaking current
20 / 25 / 31.5 kA
Opening / closing time
30–60 ms / 50–100 ms
Rated breaking operations
20
Mechanical life
10000 次 ops

Specifications are representative and may vary by configuration and region. Final figures are confirmed on the project datasheet.

Ready to power your next project?

Tell us about your load profile and site conditions — our engineers will help you size the right HiStore configuration.