Air & Solid-Insulated RMU

HP-SIS-12 Solid-Insulated Ring Main Unit

Fully insulated, fully enclosed, maintenance-free vacuum RMU — epoxy-cast live parts and solid insulated busbars, ideal for harsh environments from high altitude to heavy pollution.

Factory-direct supply Worldwide delivery & export documentation 12-month warranty · extended options
  • Rated voltage (kV) · rated current (A) · switch type (C load switch / V breaker / G disconnector / F load-swit
At a glance

Built to perform, year after year

12 kV / 50 Hz
Rated voltage / frequency
630 / 1250A
Rated current
48 / 42 / 42kV
PF withstand (break / ph-ph / ph-E)
85 / 75 / 75kV
Impulse withstand (break / ph-ph / ph-E)
A closer look

Engineered around safety, efficiency and uptime

Overview

All high-voltage live parts of the HP-SIS-12 are cast in epoxy resin of excellent insulating performance, integrating the vacuum interrupter, main conductive circuit and insulating supports into one solid body; functional units are linked by fully insulated solid busbars. The switchgear is therefore immune to external environment, ensuring equipment reliability and operator safety.

Applications

Simple structure, flexible operation, reliable interlocking and easy installation for 50 Hz / 12 kV systems. Widely used in industrial and civil cable ring networks and terminal distribution: urban residential supply, small substations, switching stations, cable branch boxes, box substations, factories, malls, airports, metros, wind farms, hospitals, stadiums, railways and tunnels. Full insulation, sealing and shielding make it especially suitable for high-altitude, hot-humid, severe-cold and heavily polluted areas.

Model designation

Rated voltage (kV) · rated current (A) · switch type (C load switch / V breaker / G disconnector / F load-switch-fuse combination) · B without earthing switch / Z lower vertical outlet · rated short-time withstand current (kA)

Technical specifications

Full specifications

Technical parameters
Rated voltage / frequency
12 kV / 50 Hz
Rated current
630 / 1250 A
PF withstand (break / ph-ph / ph-E)
48 / 42 / 42 kV
Impulse withstand (break / ph-ph / ph-E)
85 / 75 / 75 kV
Rated short-circuit breaking current
25 / 31.5 kA
Rated short-time withstand current
25 / 31.5 kA
Peak withstand / making current
63 / 80 kA
Protection degree / operation
IP4X · 弹簧储能 Spring
Cabinet dimensions (W×D×H, mm)
Load-switch PT cabinet (CPT)
500×950×1650
Breaker cabinet (V / VB / VZ)
400×950×1650
Bus riser cabinet (G)
400×950×1650
Load-switch fuse cabinet (F)
500×950×1650

Specifications are representative and may vary by configuration and region. Final figures are confirmed on the project datasheet.

Ready to power your next project?

Tell us about your load profile and site conditions — our engineers will help you size the right HiStore configuration.